Closed foam water sprinkler device
Category:
Closed Foam Water Sprinkler Device
Key words:
Foam Fire Extinguishing System
Product details
PZBS closed foam water sprinkler device is organically combined with the automatic sprinkler system and the pressure foam proportioning device. When the fire occurs, the automatic sprinkling system starts. The system water is mixed with the water film foaming raw water through the proportioning device to form a water film foam mixture (3% or 6%). The mixture is sprayed into the protected area through the sprinkler to extinguish the fire. The system is designed to protect the place where a, b and c liquid leakage leads to overflow fire.It can cool the surface of the protection object, block the radiation heat and cover the asphyxiation fire.
Main performance and parameter talbe:
|
Model |
Mixture flow range(L/S) |
Mixing ratio(%) |
Working Pressure(Mpa) |
Pressure drop(Mpa) |
Foam injection timet(min) |
Storage tank volume(L) |
Connection flange |
|
PZBS 32/10(3%) |
4~32 |
3 |
0.6~1.2 |
Less than 0.15 |
T=V/60qλ V: tank volume Q: mixture flow λ: mixture ratio |
1000 |
DN150 |
|
PZBS 32/10(6%) |
4~32 |
6 |
1000 |
||||
|
PZBS 32/15(6%) |
4~32 |
1500 |
|||||
|
PZBS 40/20(6%) |
8~40 |
2000 |
|||||
|
PZBS 40/15(3%) |
10~40 |
3 |