UT0003 Upright Sprinkler

Upright sprinkler is designed for use in automatic sprinkler systems designed in accordance with standard installation (NFPA13). The temperature response is standard response 5mm glass bulb and fast response 3mm glass bulb. The sprinklers come with compact design. available in different finishes and temperature ratings. APPROVALS:UL

Category:

Sprinklers (UL/FM)

Key words:

UL LISTED SPRINKLER

Product details

DESCRIPTION

Upright sprinkler is designed for use in automatic sprinkler systems designed in accordance with standard installation (NFPA13). 

The temperature response is standard response 5mm glass bulb and fast response 3mm glass bulb. The sprinklers come with compact design. available in different finishes and temperature ratings.

Sprinklers are installed with adjustable or non- adjustable escutcheon plates. These are intended to be installed finished ceilings. Escutcheon plate adjustment provides convenience in pendent and conventional sprinkler installation in case of areas with finished ceiling or walls.

 

 

Features

 

 

• UL and C-UL Listed; FM Approved; CCC • Standard Response
• Multiple temperature ratings and finishes available • K-factor 5.6
• Operates with 5mm frangible glass bulb  

 

 

Technical Specification

 

 

Sprinkler Identification Number (SIN) UT0003
Response Standard
Temperature Rating / Color / Classification 135°F (57°C) / Orange / Ordinary
155°F (68°C) / Red / Ordinary
175°F (79°C) / Yellow / Intermediate
200°F (93°C) / Green / Intermediate
286°F (141°C) / Blue / High
Discharge Coefficient GPM / psi½ (LPM/bar½) K=5.6 (80)
Nominal Thread Size 1/2" NPT / 1/2" BSPT
Max. Working Pressure 175 PSI (12BAR)
Factory Testing Pressure 500 PSI (35BAR)
Min. Operating Pressure 7 PSI (0.5 BAR)
Finishes Brass, White Coating and Chrome